GENERAL: |
|
Design Topology: |
IGBT & MOSFET / Pulse Width Modulated (PWM) Inverter / Rectifier Solid State Design |
Electrical Configuration: |
Single Phase 2 Wire (1 Phase + Neutral + G / E) |
Power Ratings: |
2.1 kVA (9.1 Amps), 3.5 kVA (15.2 Amps), 5.25 kVA (22.8 Amps), 7 kVA (30.4 Amps), 10.5 kVA (45.6 Amps) & 14 kVA (60.8 Amps) |
Power Factor: |
The Power Factor has no effect on performance providing the stabiliser is being used within its rated capacity |
Frequency |
50 / 60 Hz |
INPUT: |
|
Voltage |
230 V |
Frequency |
50 / 60 Hz |
Permissible Input Voltage Window |
230V ±25% (173V to 287V) |
OUTPUT: |
|
Voltage: |
230V |
Voltage Regulation: |
±1% |
Frequency |
50 / 60 Hz |
METERING / STATUS: |
|
Frequency |
|
LCD Digital Metering: |
Input & Output Volts,
Input & Output Frequency
Output Current (Amps) & Load Level (%)
Internal Temperature (°C) |
Status Indicators: |
Normal Operation Available
Stable Output Voltage
Overload of Fault - In Automatic Electronic Bypass Mode
Overload or the existence of an abnormal condition |
Audible Alarms: |
Fault and Over Voltage |
Communications: |
RS-232 Serial Port |
PROTECTION FEATURES: |
|
Over Current: |
Input & Output Breakers - as Standard |
Spike & Surge Protection: |
MOV (Metal Oxide Varistor) |
Noise Protection: |
EMI Filters |
Overload Protection: |
More than 105% Output Automatically Disconnected - requiring Manual Restart (Output Under Limit 188V ±4V, Over Limit 270V ±4V) |
Over & Under Voltage Protection: |
Protects against high and low voltage with automatic output disconnection requiring manual restart |
Short Circuit Protection: |
Automatic output disconnect requiring manual restart |
Manual Maintenance Bypass - Inbuilt: |
Fitted as standard on 3.5 kVA Models and Above.
The ability to manually re-route the supply feed to bypass the stabilisation function |
ENVIRONMENTAL: |
|
Operating Temperature Range: |
0 to 40°C. Derate by 2% for each additional °C Up to max 60°C |
Storage Temperature Range: |
-20 to 50°C |
Maximum Altitude: |
2000 Metres. Derate by 1% for each additional 100m |
Relative Humidity: |
Suitable for indoor use up to 90% Relative Humidity (non-condensing) |
Cooling: |
Forced fan cooling |
Acoustic Noise Level: @1 Metre: |
<50 dbA |
PHYSICAL: |
|
Construction: |
Sheet metal enclosure to IP20 / NEMA 1 Style - BS EN 60529 - with Plastic Molded Front Cover |
Colour: |
RAL 7047 (Telegray 4) |
Dimensions: - W x D x D (mm) |
2.1 kVA - 258 x 333 x 422 | 3.5 kVA - 258 x 333 x 422 | 5.25 kVA - 258 x 333 x 422 | 7 kVA - 258 x 333 x 422 | 10.5 kVA - 258 x 546 x 531 | 14 kVA - 258 x 546 x 531 |
Packed: - W x D x D (mm) |
2.1 kVA - 39 x 45 x 54 | 3.5 kVA - 39 x 45 x 54 | 5.25 kVA - 39 x 45 x 54 | 7 kVA - 39 x 45 54 | 10.5 kVA - 41 x 78 x 68 | 14 kVA - 41 x 78 x 68 |
Weight: (Packed) - W x D x D (mm) |
2.1 kVA - 23 Kg (26 Kg) | 3.5 kVA - 29 Kg (32 Kg) | 5.25 kVA - 30 Kg (33 Kg) | 7 kVA - 32 Kg (35 Kg) | 10.5 kVA - 58 Kg (69 Kg) | 14 kVA - 62 Kg (73 Kg) |
CERTIFICATION & CONFORMANCE: |
|
EMC Conformance: |
BS EN 55022 and relevant parts of BS EN 61000 |
CE Certification: |
Fully Compliant - 2014/30/EU (The EMC Directive) and 2014/35/EU (The Low Voltage Directive) |
WARRANTY: |
|
Standard Warranty: |
24 Months / 2 Years from date of supply |