GENERAL |
|
Design Topology: |
Static -Digital Buck-Boost SCR Design |
Electrical Configuration: |
Three Phase, 4 Wire, (3 Phase + Neutral + G/E) |
Power Ratings: |
250 kVA, 300 kVA, 350 kVA, 400 kVA, 450 kVA,
500 kVA, 600 kVA, 650 kVA, 700 kVA, 750 kVA,
800 kVA, 900 kVA, 1000 kVA, 1200 kVA, 1250 kVA,
1500 kVA, 1600 kVA, 2000 kVA, 2500 kVA, 3000 kVA
3125 kVA & 3750 kVA
- smaller ratings to order |
Power Factor: |
The Power Factor has no effect on performance providing
the stabiliser is being used within its rated capacity |
Frequency: |
35 to 63Hz |
INPUT |
|
Voltage: |
380/220V - 400/230V - 415/240V (Customer to Specify) |
Voltage Swing Options
Available: |
±15% (S15 Models - up to 3750 kVA)
±20% (S20 Models - up to 3750 kVA)
±25% (S25 Models - up to 2500 kVA)
±30% (S30 Models - up to 2000 kVA)
±35% (S35 Models - up to 1200 kVA)
±40% (S40 Models - up to 1200 kVA)
±45% (S45 Models - up to 1200 kVA)
±50% (S50 Models - up to 1000 kVA)
(Customer to Specify) |
Frequency: |
35 to 63Hz |
OUTPUT |
|
Voltage: |
380/220V - 400/230V - 415/240V
(Customer to Specify) |
Voltage Regulation: |
S15 to S20 Models ±3% (Default) - Adjustable ±1 to ±5%
S25 to S40 Models ±3% (Default) - Adjustable ±3 to ±5%
S45 to S50 Models ±5% |
Frequency: |
35 to 63Hz |
Response Time: |
<0.04 seconds |
Correction Time: |
40 msec per Step |
PROTECTION FEATURES |
|
Surge Suppression: |
TVSS - Protects loads against high energy
Spikes and Transient Voltages |
SPD Surge Arrestors: |
Class 2 Type Surge Protection Device - protects the load
and stabiliser against high energy voltage spikes of
operational or atmospheric origin (eg. Lightning induced spikes) |
Independent Phase
Control: |
Maintains each phases voltage stable irrespective of load
unbalance, even up to 100% load unbalance |
Start-Up Protection: |
Protection of the load equipment from damaging start up
voltage surges |
Automatic Bypass: |
Automatic transfer to bypass in the event of an
overload or system problem |
Overload Capacity: |
5 x max. current rating for 1 second
1.5 x max. current rating for 1 minute |
Short Circuit & Overload
Switch / Breaker Protection
and Manual Bypass
facility: |
250 to 400 kVA Rated Models
Type 1 (T1) style switch arrangement
consists of an input switch and bypass switch, with output
isolation, with mechanical interlocking to prevent
inadvertent mis-operation
450 to 2000 kVA Rated Models
Type 2 (T2) style switch arrangement consists of a
motorised input air switch and output / bypass changeover
switch, with full electronic interlocking to prevent inadvertent
mis-operation
2500 kVA + Rated Models
Type 3 (T3) style switch arrangement similar to the
Type 2 arrangement, but utilising separate motorised
air output and bypass switches, with full electronic interlocking
to prevent inadvertent mis-operation
For further details see Breaker / Switch Configurations and
Control Panels Tab below |
ENVIRONMENTAL |
|
Operating Temperature
Range: |
Temperature range 0 to 45 °C
Derate by 2% for each additional °C Up to max 60 °C |
Maximum Altitude: |
Maximum altitude 4000m
Derate by 2.5% for each additional 500m |
Relative Humidity: |
Suitable for indoor tropical use 90% RH (non-condensing) |
Efficiency: |
=>98% |
THD - Harmonic Distortion: |
None introduced |
Audible Noise: |
< 45 dB (at 1 Metre) |
PHYSICAL |
|
Construction: |
Enclosures to IP20 (NEMA 1 Style) - BS EN 60529 |
Colour: |
RAL 7032 (Pebble Grey - Epoxy Powder Coating) |
Dimensions & Weights: |
See S15 to S50 Tabs below |
CONFORMANCE |
|
EMC Conformance: |
Complies with BS EN 55022 and the relevant parts of
the BS EN 61000 series of standards |
CE Certification:: |
CE Marked - being fully compliant with European Union
Directives 2014/30/EU (The EMC Directive) and
2014/35/EU (The Low Voltage Directive) |
WARRANTY |
|
Standard Warranty: |
2 Year / 24 Months from date of supply |
Extended Warranty: |
Option - Extendable Warranty up to 60 Months / 5 Years |
ADD-ON OPTIONS |
|
Input Isolating
Transformer:
(-PC) |
Through the inclusion of a shielded isolation transformer,
provides enhanced spike & electrical noise (common &
normal interference) suppression and neutral
ground bonding. Delivers what is commonly
referred to as a ‘CLEAN’ supply |
Outdoor IP54
Ingress Protection:
(-IP54) |
Stabiliser presented in an endurable IP54 (BS / EN 60529)
/ NEMA 3 free standing steel cubicles suitable for
external use, or more challenging internal environments |
AquaStop:
(-AS) |
PCB protective coating offering protection against
damp and moisture ingress |
Alternative Switch
Arrangements:
(-T2 or T3) |
Alternative Input, Output and Bypass Switching arrangements
- T2 (250 to 400 kVA)
- T3 (250 to 2000 kVA)
See Short Circuit & Overload Switch / Breaker Protection
and Manual Bypass facility Section above |
Additional Metering:
(-ADM) |
Additional Digital Metering for
- Input Volts
- Frequency
- Power Factor |
4 Pole Switches / Breakers:
(-FP) |
As standard ESR Stabilisers utilise 3 Pole Switches / Breakers.
As an option 4 Pole alternatives can be supplied. |
eSpec Upgrade:
(-eSP) |
While we endeavour to keep production costs to a minimum
by sourcing top specification components from
around the globe we realise that some clients have a
requirement for their own designated protection devices
Accordingly we are able to offer our eSpec Pack Upgrade
package which offers the client the short circuit and
overcurrent protection components from their preferred
leading European or American manufacturers |